Technical Information
Key features of the FBM207/b/c modules are: -Sixteen discrete inputs -Supports discrete input signals at voltages of: • 15 to 60 V dc - contact sense • 120 V ac/125 V dc - voltage monitoring or switch inputs • 240 V ac - voltage monitoring or switch inputs -Each input is galvanically isolated. Group isolated with external excitation -Single or redundant modules -Compact, rugged design suitable for enclosures in Class G3 (harsh) environments -Executes
programs for Discrete Input, Ladder Logic, Pulse Count, and Sequence of
Events with configurable Input Filter Time option -Termination Assemblies (TAs) for locally or remotely connecting field wiring to the FBM207 -Termination Assemblies for per channel internally and/or externally loop powered devices -Various
Termination Assemblies (TAs) have additional signal conditioning
hardware that provides voltage attenuation and optical isolation.
|
|
|
|
|
|
|